Triathlon III UPS

3 Phase Input to 1 Phase Output Model   (download PDF)

MODEL T3UPS-31-30K
CAPACITY KVA 30 KVA
INPUT Voltage
(select one individual voltage)
3 Phase Delta 220/380/460 ± 20%
3 Phase Wye 190/200/208/220/230/240V ± 20%
3 Phase Wye 380/400/415/440/460/480V ± 20%
Frequency (select one) 50 or 60 Hz ± 5% (Optional 400Hz)
Power Factor >= 0.97
Power Walk In 0-100%: 20 seconds
OUTPUT Voltage
(select one individual voltage)
100, 110, 115, 120, 200, 208, 220, 230, or 240V ( ± 5% adjustable)
Voltage Regulation ± 1% at Linear Load
Phase Shift (unbal. load) < 0.5 Deg.
Frequency (select one) 50 or 60Hz ±0.1 Hz (Optional 400 Hz)
Power Factor 0.8
Distortion (THD) < 2.0% (Linear Load)
Crest Factor 3:1
Overload Capacity 125% for 15 Minutes, 150% for 10 Minutes, > 150% for 1 Minute
Efficiency >= 91%
INDICATORS LCD Real Time Status, Data or Historical Events, Parameters, Real Time Clock, Inverter & Alarm
LED Up to date information (Status) to the User & Audible Alarm
PROTECTION Over/Under Voltage Alarm
Output Short Circuit Auto-shutdown
Overload Auto-shutdown 25 sec. later
Over Temperature Auto-shutdown
Surge Surge and Lightning Protection
EMI/EMC EN50091-2 Approved
Galvanic Isolation Input & Output True Galvanic Isolation
INTERFACE Contact Closure, RS-232/485  Supports MEGATEC RUPS, UPSilon 2000 UPS monitoring software
ENVIRONMENT Operating Temperature 0° – 40° C
Humidity 0 - 90% Non-condensing
Audible Noise < 65 dB at 1 meter
DIMENSIONS W x H x D (mm) 1,100*1,600*800
W x H x D (in) 43.3*63.0*31.5
WEIGHT * Kilograms 580
Pounds 1278.7
BATTERY Type - Quantity 26AH - 29
BACKUP TIME ** Minutes - Minimum 10 min.
BATTERY CABINET DIM W x H x D (mm) 550*1,600*800
W x H x D (in) 21.7*63.0*31.5
BATTERY CABINET WEIGHT Kilograms 142
Pounds 313.1
BATTERY WEIGHT Kilograms 268
Pounds 590.8
* Weights based on 220/380V IN and 220V OUT. Weights may vary based on input/output frequency/volt
** Longer backup times (to 8 hours) are available from standard models; custom specifications also available.