Triathlon III UPS

1 Phase Input to 1 Phase Output Model   (download PDF)

MODEL T3UPS-11-15K
CAPACITY KVA 15 KVA
INPUT Voltage
(select one individual voltage)
1 Phase 100, 110, 115, 120, 200, 208, 220, 230, or 240V ± 20%
Frequency (select one) 50 or 60 Hz ± 5% (Optional 400Hz)
Power Walk In 0-100% < 20 seconds
OUTPUT Voltage
(select one individual voltage)
100, 110, 115, 120, 200, 208, 220, 230, or 240V ( ± 5% adjustable)
Voltage Regulation ± 1% at Linear Load
Frequency (select one) 50 or 60Hz ± 0.1Hz (Optional 400Hz)
Phase 1 Phase, 2W+G (Optional 3W)
Power Factor 0.8
Distortion (THD) < 2% @ 0-100% Non-linear Load
Crest Factor 3:1
Overload Capacity 125% for 15 Minutes, 150% fro 10 Minutes, > 150% for 1 minute
Efficiency >=91%
INDICATORS LCD Real Time Status, Data or Historical Events, Parameters, Real Time Clock, Inverter & Alarm
LED Up to date information (Status) to the User & Audible Alarm
PROTECTION Over/Under Voltage Alarm
Output Short Circuit Rectifier, Reserve, Bypass NFB
Overload Auto-shutdown 1 minute, Auto Restore when back to normal
Over Temperature Auto-shutdown
Surge MOV / Input & Output (FCC CLASS A)
EMI/EMC EN50091-2 Approved
Galvanic Isolation Input & Output True Galvanic Isolation
INTERFACE Contact Closure, RS-232/485  Support MEGATEC RUPS, MEGATEC RUPSII / UPSilon 2000 UPS monitoring software
ENVIRONMENT Operating Temperature 0° – 40° C
Humidity 0 - 90% Non-condensing
Audible Noise < 65 dB at 1 meter
DIMENSIONS W x H x D (mm) 550*1,600*800
W x H x D (in) 21.7*63.0*31.5
WEIGHT* w/o batteries Kilograms 320
Pounds 705.5
BATTERY WEIGHT Kilograms 170
Pounds 374.8
BATTERY Type - Quantity HR1234W - 58
BACKUP TIME ** Minutes - Minimum 15 min.
* Weights based on 220V IN and OUT. Weights may vary based on input/output frequency/voltage
** Longer backup times (to 8 hours) are available from standard models; custom specifications also available.