Triathlon III Frequency Converter

3 Phase Input to 3 Phase Output Model   (download PDF)

MODEL T3FC-33-1000K
CAPACITY KVA 1000 KVA
INPUT Voltage
(select one individual voltage)
3 Phase Delta 220/380/460 ± 20%
3 Phase Wye 190/200/208/220/230/240V ± 20%
3 Phase Wye 380/400/415/440/460/480V ± 20%
Frequency 47 - 63 Hz (400 Hz. Optional)
Power Walk In 0-100%: 20 seconds
OUTPUT Voltage
(select one individual voltage)
3 Phase Delta 220/380/460V
3 Phase Wye 190/200/208/220/230/240V
3 Phase Wye 380/400/415/440/460/480V
(± 15% adjustable from nominal)
Voltage Regulation ± 1% at Linear Load
Phase Shift (unbal. load) < 0.5 Deg.
Frequency (select one) 50 or 60Hz ± 0.1Hz
(Optional: 400Hz.)
(Optional: Switch Selectable 50/60Hz.)
(Optional: Frequency Adjustable ±10% from nominal)
Power Factor 0.8
Distortion (THD) < 5.0% (Linear Load)
Crest Factor 3:1
Overload Capacity 125% for 15 Minutes, 150% fro 10 Minutes, > 150% for 1 minute
Efficiency = 94%
INDICATORS LCD Real Time Status, Data or Historical Events, Parameters, Real Time Clock,
Inverter & Buzzer
LED Up to date information (Status) to the User & Audible Alarm
PROTECTION Over/Under Voltage Alarm
Output Short Circuit Current Limited and cut-off, fuse and breaker
Overload Auto-shutdown 1 Minute. Auto Restore when back to normal
Over Temperature Auto-shutdown
Lightning / EMC Filter MOV / Input & Output (FCC CLASS A)
EMI/EMC EN50091-1, -2 Approved
Galvanic Isolation Input & Output True Galvanic Isolation
INTERFACE Contact Closure, RS-232/485 Supports Remote Control Module, Optional SNMP card (Model No. MEGATEC Net Agent II)
ENVIRONMENT Operating Temperature 0° – 40° C
Humidity 0 - 90% Non-condensing
Audible Noise < 90 dB at 1 meter
DIMENSIONS W x H x D (mm) 4,520*1,900*1,250
W x H x D (in) 180.0*74.8*49.2
WEIGHT Kilograms 7,800
Pounds 17,196
* Weights based on 220/380V IN and OUT. Weights may vary based on input/output frequency/voltage