Triathlon II AC Power Source

1 Phase Input to 1 Phase Output Model   (download PDF)

MODEL T2FC-11-45K
Output KVA 45 KVA
INPUT Voltage
(select one individual voltage)
1 Phase 2W 110/120/220/230/240V ± 10%
Frequency 47-63 Hz
Power Factor 0.6 - 0.7
OUTPUT Voltage 110V Setting: 0-150V (Low Range)
220V Setting: 0-300V (High Range) (optional 0-600V)
Voltage Regulation <= 1%
Current Limit L-N at 120 V L: 375A
L-N at 240 V H: 187.5A
Frequency 47-63 Hz (Optional 40 to 500 Hz)
Power Factor 0.8
Distortion (THD) <= 2%
Crest Factor 3:1
Overload Capacity 120% > 2 sec., 120-150% 2 sec., 200% Instant Trip
Efficiency > 80%
INDICATORS LED Freq. (0.1 Hz), Volt (0.1V), Amp (0.1A), Power (0.1W)
PROTECTION Output Short Circuit Electronic circuit breaker
Overload Electronic circuit breaker
Over Temperature Electronic circuit breaker instant cut off
EMI/EMC Output Filter
ENVIRONMENT Operating Temperature 0° – 40° C
Humidity 0 - 90% Non-condensing
Audible Noise < 45 dB at 1 meter
DIMENSIONS W x H x D (mm) 860*1,600*590
W x H x D (in) 33.9*63.0*23.2
WEIGHT * Kilograms 300
Pounds 661.4
* Weights may vary based on input/output frequency/voltage/phase