Triathlon II AC Power Source

3 Phase Input to 3 Phase Output Model   (download PDF)

MODEL T2FC-33-100K
Output KVA 100 KVA
INPUT Voltage
(select one individual voltage)
3 Phase Wye 190/200/208/220/230/240/380/400/415/440/460/480V +/- 10%
3 Phase 3W Delta 220/230/240/380/400/415/440/460/480V +/- 10%
Frequency 47-63 Hz
Power Factor 0.6 - 0.7
OUTPUT Voltage 0-260V, L-L:0-150V, L-N (Low Range)
0-520V,L-L: 0-300V, L-N (High Range) (optional 0-600V, L-L)
Voltage Regulation <= 1%
Current Limit L-N at 120 V L: 277.6A
L-N at 240 V H: 138.8A
Frequency 47-63 Hz (Optional 40 to 500 Hz)
Power Factor 0.8
Distortion (THD) <= 2%
Crest Factor 3:1
Overload Capacity 120% > 2 sec., 120-150% 2 sec., 200% Instant Trip
Efficiency > 80%
INDICATORS LED Freq. (0.1 Hz), Volt (0.1V), Amp (0.1A), Power (0.1W)
PROTECTION Output Short Circuit Electronic circuit breaker instant cut off
Overload Electronic circuit breaker instant cut off
Over Temperature Electronic circuit breaker instant cut off
EMI/EMC Output Filter
ENVIRONMENT Operating Temperature 0° – 40° C
Humidity 0 - 90% Non-condensing
Audible Noise < 45 dB at 1 meter
DIMENSIONS W x H x D (mm) 1,200*1,950*800
W x H x D (in) 47.2*76.8*31.5
WEIGHT * Kilograms 720
Pounds 1587.3
* Weights may vary based on input/output frequency/voltage/phase