Phone: (800)523-9938

Triathlon III Frequency Converter

1 Phase Input to 1 Phase Output Model   (download PDF)

MODEL T3FC-11-20K
CAPACITY KVA 20 KVA
INPUT Voltage
(select one individual voltage)
1 Phase 100, 110, 115, 120, 200, 208, 220, 230, or 240V ± 20%
Frequency 47 - 63 Hz (Optional 400Hz)
Power Walk In 0-100% < 20 seconds
OUTPUT Voltage
(select one individual voltage)
100, 110, 115, 120, 200, 208, 220, 230, or 240V
(± 15% adjustable from nominal)
Voltage Regulation ± 1% from Set Point
Phase Shift (unbal. load)  
Frequency (select one) 50 or 60Hz ± 0.1Hz
(Optional: 400Hz.)
(Optional: Switch Selectable 50/60Hz.)
(Optional: Frequency Adjustable ±10% from nominal)
Power Factor 0.8-1 lag
Distortion (THD) < 2.0% (Linear Load)
Crest Factor 3:1
Overload Capacity 125% for 15 Minutes, 150% fro 10 Minutes, > 150% for 1 minute
Efficiency > 85%
INDICATORS LCD Real Time Status, Data or Historical Events, Parameters, Real Time Clock, Inverter & Alarm
LED Up to date information (Status) to the User & Audible Alarm
PROTECTION Over/Under Voltage Alarm
Output Short Circuit Current Limited and cut-off, fuse and breaker
Overload Auto-shutdown 1 minute, Auto Restore when back to normal
Over Temperature Auto-shutdown
Lightening/EMC Filter MOV / Input & Output (FCC CLASS A)
EMI/EMC EN50091-1, -2 Approved
Galvanic Isolation Input & Output True Galvanic Isolation
INTERFACE Contact Closure, RS-232/485  Supports Remote Control Module,
Optional SNMP card (Model No. MEGATEC Net Agent II
ENVIRONMENT Operating Temperature 0° – 40° C
Humidity 0 - 90% Non-condensing
Audible Noise < 65 dB at 1 meter
DIMENSIONS W x H x D (mm) 550*1,600*800
W x H x D (in) 21.7*63.0*31.5
WEIGHT * Kilograms 400
Pounds 881.8
* Weights based on 220V IN and 380V OUT. Weights may vary based on input/output frequency/voltage