| MODEL | T3FC-11-10K | ||
|---|---|---|---|
| CAPACITY KVA | 10 KVA | ||
| INPUT | Voltage (select one individual voltage) |
1 Phase 100, 110, 115, 120, 200, 208, 220, 230, or 240V ± 20% | |
| Frequency | 47 - 63 Hz (Optional 400Hz) | ||
| Power Walk In | 0-100% < 20 seconds | ||
| OUTPUT | Voltage (select one individual voltage) |
100, 110, 115, 120, 200, 208, 220, 230, or 240V (± 15% adjustable from nominal) |
|
| Voltage Regulation | ± 1% from Set Point | ||
| Phase Shift (unbal. load) | |||
| Frequency (select one) | 50 or 60Hz ± 0.1Hz (Optional: 400Hz.) (Optional: Switch Selectable 50/60Hz.) |
||
| Power Factor | 0.7-1 lag | ||
| Distortion (THD) | < 3.0% (Linear Load) | ||
| Crest Factor | 3:1 | ||
| Overload Capacity | 110% continuous, 120-150% for 30 sec., > 150% auto-shutdown, auto restart when normal | ||
| Efficiency | > 85% | ||
| INDICATORS | LCD | I/P&O/P Voltage, I/P&O/P Frequency, Loading %, History Record | |
| LED | Utility LED (green), Inverter LED (green), Fault LED (red), Overload (yellow) | ||
| PROTECTION | Over/Under Voltage | Alarm | |
| Output Short Circuit | Current Limited and cut-off, fuse and breaker | ||
| Overload | 150% 30seconds cut off (Current Limited) | ||
| Over Temperature | Auto-shutdown | ||
| Lightening/EMC Filter | Surge and Lightning Protection | ||
| EMI/EMC | EN50091-2, CE Approved | ||
| Galvanic Isolation | N/A | ||
| INTERFACE | Contact Closure, RS-232 | Support MEGATEC RUPS, MEGATEC RUPSII / UPSilon 2000 UPS monitoring software | |
| ENVIRONMENT | Operating Temperature | 0° – 40° C | |
| Humidity | 0 - 90% Non-condensing | ||
| Audible Noise | < 45 dB at 1 meter | ||
| DIMENSIONS | W x H x D (mm) | 480*845*340 | |
| W x H x D (in) | 18.9*33.3*13.4 | ||
| WEIGHT * | Kilograms | 116 | |
| Pounds | 255.7 | ||
| * Weights based on 220V IN and 380V OUT. Weights may vary based on input/output frequency/voltage | |||