Phone: (800)523-9938

Triathlon III Frequency Converter

1 Phase Input to 1 Phase Output Model   (download PDF)

MODEL T3FC-11-8K
CAPACITY KVA 8 KVA
INPUT Voltage
(select one individual voltage)
1 Phase 100, 110, 115, 120, 200, 208, 220, 230, or 240V ± 20%
Frequency 47 - 63 Hz (Optional 400Hz)
Power Walk In 0-100% < 20 seconds
OUTPUT Voltage
(select one individual voltage)
100, 110, 115, 120, 200, 208, 220, 230, or 240V
(± 15% adjustable from nominal)
Voltage Regulation ± 1% from Set Point
Phase Shift (unbal. load)  
Frequency (select one) 50 or 60Hz ± 0.1Hz
(Optional: 400Hz.)
(Optional: Switch Selectable 50/60Hz.)
Power Factor 0.7-1 lag
Distortion (THD) < 3.0% (Linear Load)
Crest Factor 3:1
Overload Capacity 110% continuous, 120-150% for 30 sec., > 150% auto-shutdown, auto restart when normal
Efficiency > 85%
INDICATORS LCD I/P&O/P Voltage, I/P&O/P Frequency, Loading %, History Record
LED Utility LED (green), Inverter LED (green), Fault LED (red), Overload (yellow)
PROTECTION Over/Under Voltage Alarm
Output Short Circuit Current Limited and cut-off, fuse and breaker
Overload 150% 30seconds cut off (Current Limited)
Over Temperature Auto-shutdown
Lightening/EMC Filter Surge and Lightning Protection
EMI/EMC EN50091-2, CE Approved
Galvanic Isolation N/A
INTERFACE Contact Closure, RS-232  Support MEGATEC RUPS, MEGATEC RUPSII / UPSilon 2000 UPS monitoring software
ENVIRONMENT Operating Temperature 0° – 40° C
Humidity 0 - 90% Non-condensing
Audible Noise < 45 dB at 1 meter
DIMENSIONS W x H x D (mm) 480*845*340
W x H x D (in) 18.9*33.3*13.4
WEIGHT * Kilograms 115
Pounds 253.5
* Weights based on 220V IN and 380V OUT. Weights may vary based on input/output frequency/voltage